| Unit
Sizes |
HP-N-300
to 2,500
(NEMA-US & Canada) |
300-2500-lbs/hr
(136 - 1,134 kg/hr) |
| HP-I-100
to 1,000 (IEC-European) |
100-1,000
kg/hr (225 – 2,165 lb/hr) |
| Final
Filter for Water Pump |
10-inch
Amtetek Filter; 10-Micron (Beta >5,000) |
| Motor
– Direct Drive Constant Speed |
Voltages
• 575v, 460v / 3ph / 60 Hz; NEMA
• 400v / 3ph / 50 Hz; IEC
• 330v / 3ph / 50 Hz; IEC |
| |
Speed
• 1725 – 1760 RPM; NEMA
• 1380 – 1430 RPM; IEC |
| High-Pressure
Pump Motor |
1.0
to 5.0 HP (0.75 to 4.0 kw) |
| High-Pressure
Manometer |
Dual
Scale 0-1450 psi (0-1000 bar) |
| Pressure
Relief Valve |
Adjustable
Range 360-1450 psi (25-100 bar) |
| Water
Supply Fill Valve and Safety Switches |
•
High Temperature: Opens at 120ºF (50ºC)
• Low Pressure: Opens at 23-psi (1.6 bar) |
| HP
Microprocessor Control |
•
ON/OFF, Proportional,
Proportional Plus Integral
• Capable of Setting Humidity and
Limit Set Point
• Fault Indication |
| Input
Devices |
Control,
High Limit, Air Proving |
| Humidity
Sensors |
0-10
VDC or 4-20 mADC |
| Zone
Control Valves |
Up
to (4) @ 24-volt AC |
| Zone
Safety Switches |
High-Pressure
Switch |
| Nozzle
Orifices |
0.008
- 0.012-inches (0.2 - 0.3mm) |
| Gauges |
Water
Inlet & High Pressure |
| Custom
Designed Nozzle Arrays |
Nominal
10.0 - 12.5-lbs/hr (4.55 - 5.67-kg/hr) per nozzle at 1000-psi
(69-bar) |
| Assembly
Constructed |
For
Tap or DI/RO Water |
| Vapor
Distribution System |
Stainless
Steel Pipes and Nozzles |
| Piping |
1/2"
Diameter (12.7 mm) 316 Stainless Steel |
| Control
Cabinet Construction |
16-
and 18-gauge (1.52 and 1.21-mm) Powder-Coated Steel |
| Shipping
Weight |
HP-N-300
125-lbs (57-kg); HP-N-2,500 250-lbs (113.4-kg) |
| Inlet
Water Supply Connection |
9