Herricane CS Series Steam Distribution System H E R R I C A N E®
Steam Distribution Systems
Quiet, Solid Reliability

Product Series
Series CS 1000 Series CS 2000 Series CS 3000 Series CS 4000

Self-Generating Steam
The use of a low pressure source of steam, such as a self contained electrode boiler requires some special installation considerations with regard to duct air velocity, duct static pressure and interconnecting plumbing between the steam generating unit and the steam distribution unit and the steam distribution system. Following the instructions below will insure a trouble-free installation.

1
Manifolds, header, and nozzles are all stainless steel material.
2
Manifold trap required on CS-2000, CS-3000 and CS-4000 series units. Trap not required on CS-1000 series units.
3
CS-58 collection header may be used to connect a dual outlet steam tank to a single 2" hose or tube for connection to a distribution system.
4
MDD units require a separate distribution system for each cylinder.
5
Exact number of steam distributor tubes may vary.
6
Exact number of steam nozzles per distributor tube may vary.
7
Duct static pressure: 5" H20
8
Air Velocity: <2000 fpm
9
Steam outlets on steam cylinder are 1 1/2" O.D. Recommended supply lines are 1 1/2" Insulated Type L Copper Pipe with 1 1/2" Hose cuffs for single steam outlet (units to 50 lbs/hr) and 2" I.D. insulated copper pipe for two outlet units (units with capacity from 51-100 lbs/hr)
10
Unit shown with CS-1101. Other CS Series may also be used.
11
Plumbing from unit to steam distribution system provided by others.