| 15781
HUMIDIFIERS
PART
1 GENERAL
A. SCOPE
[Go
to top of page]
- Furnish
and install as indicated on the drawings an in-duct atomizing
humidification and evaporative cooling system complete with
Controls Cabinets, Modulating Control Sections, and Atomizing
Manifold Assembly. Note control cabinets and modulating
control section may be supplied as one cabinetized U.L. approved
assembly.
- Warranty
system for a period of one year from date of startup.
- Provide
owner's manual to cover installation, startup, operating and
maintenance instructions.
- Water quality
is essential to operation of unit. Complete water analysis to
be provided to manufacturer for recommendations to enhance performance
and minimize maintenance.
- Refer to
schedule on drawings for capacities.
PART
2 PRODUCT
A. CONTROL
CABINET
[Go
to top of page]
- Factory
fabricated and tested.
- All internal
components prewired and prepared to terminals, ready for field
connections.
- ON-OFF
switch with "Power ON" lamp.
- Standalone
systems provide supply and return air humidity readings.
- Relay for
each stage of control allowing stages to be controlled in parallel
or series.
- Controls
to incorporate a clean-out cycle time to keep the heads clean
and in working order.
- Optional
- The system shall incorporate an automatic blow-down technique
to empty the water lines of all liquid on shutdown to prevent
freezing.
B. MODULATING
CONTROL SECTIONS
[Go
to top of page]
- Each humidification
system shall consist of two control sections; one for compressed
air supply and the other for modulating water supply.
- The water
control section shall consist of a ball valve, pressure regulator
with strainer, pressure gauges, water modulating valve (if used)
and a solenoid valve(s). Water pressure to the control section
shall be 50 psi and water pressure to duct manifold shall be
maintained at 40 psi minimum.
- The air
control section shall consist of a ball valve, pressure gauge,
solenoid valve, pressure regulator with strainer, and an air
pressure switch. Compressed air to the control section shall
be 60 psi and air pressure to the duct manifold shall be maintained
at 30 psi.
- If aggressive
water is supplied, the water control section will be constructed
of 300 series stainless steel components that resist degradation.
- All air
& water piping shall be type "L" copper or stainless
steel.
- Electrical
requirements are 120 volt, single phase. Maximum amp draw will
be 5 amps per control section. Other voltages are available.
C. ATOMIZING
HEAD MANIFOLD
[Go
to top of page]
- Manifold
shall be factory assembled unit consisting of air and water
piping and atomizing heads. Materials used will be based on
water quality.
- Atomizing
head capacity shall be (6), (8), (10), (12), (15) pounds of
water per hour. Larger capacity heads will not be accepted.
Heads will be positioned to provide the maximum possible distribution.
- Atomizing
heads shall be of materials not adversely affected by the purity
or aggressiveness of the water, easily disassembled for servicing
with self-cleaning and purging feature to provide a complete
drip-free operation. Average droplet size will not exceed 10
micron at 100% output and will decrease as the system modulates
downward. Documentation of droplet size available on request.
- Atomizing
heads will work on the internal mix method.
- External
mix heads and heads with external appendages are not acceptable.
- Each head
will not exceed 81 dBA when in operation.
- Single
manifold systems to have full modulation with a 30:1 turndown
ratio. Dual manifold systems to have full modulation on each
stage.
- Air/water
ratio will increase as the system modulates, which will reduce
the droplet size. Increasing or constant air/water ratios on
modulation will not be accepted.
- Manifold
length shall be as indicated on the drawings or sized by the
manufacturer to meet the calculated load.
- Air consumption
shall be a maximum of 12 SCFM free air per 100 pounds of water
atomized. Compressor shall include an appropriate safety factor.
D. OPERATING
SEQUENCE
[Go
to top of page]
- On a fall
in relative humidity (in the space or return air duct), the
space or return air transmitter shall send a signal to the controller.
- A discharge
high limit controller shall supply a signal to the controller.
- The controller
shall have an adjustable setpoint for both the return air (or
space) and high limit, and shall compare the sensed relative
humidity to the respective setpoints.
- The controller
shall output a proportional signal based on the humidity input
which is closest to its respective setpoint.
- On multi-manifold
applications, the manifolds will be modulated in parallel or
stages depending on the application.
- The system
will automatically shutdown if the airflow switch, located in
the discharge duct, is deactivated.
- A power
failure or compressor failure will automatically shut the system
down.
- If water
pressure is lost or reduced, the atomizing heads shall sputter
with no drippage. Complete loss of water supply will cause the
atomizing heads to blow air only.
PART
3 EXECUTION
A. GENERAL
[Go
to top of page]
- Install
system(s) as detailed on the drawings and/or as recommended
by the manufacturer. Shop drawings, indicating manifold sizes
and atomizing head capabilities shall be provided by manufacturer.
Certified independent air consumption (at various output levels)
and noise data shall be available.
- Manufacturer's
representative shall provide analysis, design and startup support
of the custom engineered humidification system(s).
- System
will be started by factory personnel.
- Compressed
air shall be oil free and dry. Air shall be filtered to a maximum
of 0.3 micron. Dryers and aftercoolers "applied" as
the compressor manufacturer recommends.
- Water treatment,
if supplied, demonstrates a satisfactory water supply to the
humidifier.
Herrmidicool
Systems are manufactured by Herrmidifier,
Trion Inc., 101 McNeill Road Sanford, NC 27330. |